How to read the schedule of test results

The last pages of an EICR are a table of numbers for every circuit. Here is what each column means and what a pass looks like.

The columns you will see

ColumnWhat it measures
Circuit / OCPDThe circuit name and the protective device, for example B32 for a 32 amp type B breaker
R1+R2Resistance of the line and protective conductors end to end. Confirms the earth path is continuous.
r1, rn, r2Ring circuit continuity. The three loops of a ring should be connected all the way round.
IRInsulation resistance in megohms. High is good. Below 1 MΩ on most circuits is a problem.
PolaritySwitches and fuses are in the line conductor, not the neutral. A tick means correct.
ZsEarth fault loop impedance in ohms. Must be low enough for the breaker to trip quickly in a fault.
RCD msHow fast the RCD disconnects at its rated current, in milliseconds.

A worked example

CCT 3 KITCHEN SKT B32 2.5/1.5 T&E
R1+R2 0.31 Ω IR L-E >299 MΩ ✓
Zs 0.42 Ω max 1.37 Ω ✓
RCD 30 mA 21 ms ✓

The measured Zs of 0.42 Ω is well under the maximum of 1.37 Ω for a B32 breaker, so in a fault the breaker would trip quickly. Insulation resistance is above the range of the meter, which is the best possible result. The RCD tripped in 21 milliseconds, comfortably inside the limit.

Readings that cause concern

  • Zs higher than the maximum for the device, which usually leads to a C2
  • Insulation resistance below 1 MΩ, which often leads to an FI
  • A ring circuit with a break, shown as unequal or missing r1, rn or r2 values
  • An RCD that does not trip, or trips too slowly

Terms you do not recognise are explained in the electrical glossary.

FAQ

Questions

Why does my report say LIM next to some readings?
LIM means a limitation. The inspector could not take that reading, for example because a circuit could not be isolated. The reason should be recorded on the report.