Earthing and bonding explained

Earthing and bonding are what make a fault safe. Missing bonding is one of the most common C2 findings.

Earthing

The earthing system gives fault current a low-resistance path back to the source, so the protective device trips quickly. UK homes are usually supplied with TN-C-S (PME), TN-S or TT earthing. The type is recorded on the front of your EICR.

Main protective bonding

Metal gas and water pipes entering the property are connected to the main earthing terminal with green and yellow conductors, usually 10 mm² in homes. This keeps all exposed metal at the same potential, so a fault cannot create a dangerous voltage between a tap and a radiator.

Supplementary bonding

Older bathrooms often have extra bonding between pipes and metalwork. Under current regulations it can be omitted if the bathroom circuits have RCD protection and the main bonding is in place.

Fixing missing bonding

Usually a short job: a new conductor and earth clamp at each service entry, labelled and tested. It is often done the same day as the inspection if you approve it.

FAQ

Questions

Plastic pipes: do they need bonding?
Plastic incoming services do not need main bonding. If the pipe changes to metal inside the property, the inspector will judge whether bonding is needed.